2010 ADA Standards for Accessible Design

ADA Coat Hook Height and Reach Ranges

Short answer

The ADA Standards give coat hooks no fixed height, only a reach range from 308 under Sections 603.4 and 604.8.3. With an unobstructed reach, that range is 15 in. minimum to 48 in. maximum above the finish floor.

Requirements at a glance

RuleRequirementSection
Coat hook locationWithin one of the reach ranges in 308; 604.8.3 repeats this rule for toilet compartments
Standards text
Coat hooks shall be located within one of the reach ranges specified in 308 .
603.4
Which hooks must complyOnce hooks are provided, at least one of each type complies in toilet rooms without compartments, in 213.3.1 compartments, and at required bathing fixtures
Standards text
Where coat hooks or shelves are provided in toilet rooms without toilet compartments, at least one of each type shall comply with 603.4 . Where coat hooks or shelves are provided in toilet compartments, at least one of each type complying with 604.8.3 shall be provided in toilet compartments required to comply with 213.3.1 . Where coat hooks or shelves are provided in bathing facilities, at least one of each type complying with 603.4 shall serve fixtures required to comply with 213.3.6 .
213.3.7
Unobstructed forward reachHigh reach up to 48 in., low reach down to 15 in., from the finish floor
Standards text
Where a forward reach is unobstructed, the high forward reach shall be 48 inches (1220 mm) maximum and the low forward reach shall be 15 inches (380 mm) minimum above the finish floor or ground.
308.2.1
Unobstructed side reachFrom a parallel approach: 48 in. maximum high reach and 15 in. minimum low reach
Standards text
Where a clear floor or ground space allows a parallel approach to an element and the side reach is unobstructed, the high side reach shall be 48 inches (1220 mm) maximum and the low side reach shall be 15 inches (380 mm) minimum above the finish floor or ground.
308.3.1
Forward reach over an obstruction48 in. maximum at a reach depth of 20 in. or less; 44 in. maximum for deeper reaches, up to 25 in.
Standards text
Where a high forward reach is over an obstruction, the clear floor space shall extend beneath the element for a distance not less than the required reach depth over the obstruction. The high forward reach shall be 48 inches (1220 mm) maximum where the reach depth is 20 inches (510 mm) maximum. Where the reach depth exceeds 20 inches (510 mm), the high forward reach shall be 44 inches (1120 mm) maximum and the reach depth shall be 25 inches (635 mm) maximum.
308.2.2
Side reach over an obstructionObstruction 34 in. high and 24 in. deep maximum. High reach 48 in. maximum at 10 in. depth or less, 46 in. maximum up to 24 in.
Standards text
Where a clear floor or ground space allows a parallel approach to an element and the high side reach is over an obstruction, the height of the obstruction shall be 34 inches (865 mm) maximum and the depth of the obstruction shall be 24 inches (610 mm) maximum. The high side reach shall be 48 inches (1220 mm) maximum for a reach depth of 10 inches (255 mm) maximum. Where the reach depth exceeds 10 inches (255 mm), the high side reach shall be 46 inches (1170 mm) maximum for a reach depth of 24 inches (610 mm) maximum.
308.3.2
Hooks in dressing, fitting, and locker roomsHooks within the room go within one of the reach ranges in 308
Standards text
Coat hooks provided within the room shall be located within one of the reach ranges specified in 308 .
803.5
Hook projection on a circulation path4 in. maximum where the leading edge is more than 27 in. and not more than 80 in. above the floor
Standards text
Objects with leading edges more than 27 inches (685 mm) and not more than 80 inches (2030 mm) above the finish floor or ground shall protrude 4 inches (100 mm) maximum horizontally into the circulation path.
307.2
Hooks inside the water closet clearanceCoat hooks may overlap the clearance; other fixtures and obstructions may not sit in it
Standards text
The required clearance around the water closet shall be permitted to overlap the water closet, associated grab bars, dispensers, sanitary napkin disposal units, coat hooks, shelves, accessible routes, clear floor space and clearances required at other fixtures, and the turning space. No other fixtures or obstructions shall be located within the required water closet clearance.
604.3.2

Source: 2010 ADA Standards for Accessible Design, U.S. Access Board. State and local codes can be stricter, and the authority having jurisdiction has the final word.

Finish floor0"12"24"36"48"60"15 to 48 in.Unobstructed reachADA 308.2.146 in. maxDeep side reachADA 308.3.244 in. maxDeep forward reachADA 308.2.2
Heights above the finish floor, drawn to scale. Unobstructed reach: 15 to 48 in. above the finish floor (ADA 308.2.1). Deep side reach: 46 in. max above the finish floor (ADA 308.3.2). Deep forward reach: 44 in. max above the finish floor (ADA 308.2.2).

How to check a hook against the reach range

Coat hooks have no height of their own in the Standards. Sections 603.4 and 604.8.3 point to the reach ranges in 308, and meeting any one range is enough. With nothing in the way, forward reach under 308.2.1 and side reach under 308.3.1 both run from 15 to 48 in. above the finish floor.

The Standards do not name a measuring point on the hook. Keeping the whole hook inside the range avoids an argument over which part counts. Measure from the finish floor, not from a bench seat or the bottom edge of a partition.

Obstructions change the top of the range. Over an obstruction with clear floor space extending beneath it, 308.2.2 keeps the forward limit at 48 in. for a reach depth of 20 in. or less. Deeper reaches, up to 25 in., drop it to 44 in. For a side reach, 308.3.2 lowers it to 46 in. once the reach depth passes 10 in.

Stalls, toilet rooms, and locker rooms

Section 213.3.7 applies only where coat hooks are provided. In a toilet room without compartments, at least one hook meets 603.4. Once hooks go into toilet compartments, at least one meeting 604.8.3 belongs in the compartments required to comply with 213.3.1.

Bathing facilities follow a similar pattern: at least one hook meeting 603.4 serves the fixtures required by 213.3.6. In dressing, fitting, and locker rooms, 222.2 requires at least one provided hook to meet 803.5, which uses the same reach ranges in 308.

At the water closet, 604.3.2 lets hooks overlap the required clearance, while no other fixtures or obstructions may sit there. Along a circulation path, 307.2 covers a hook with its leading edge more than 27 in. and not more than 80 in. above the floor. That hook may project 4 in. maximum.

Common mistakes with coat hooks

Mounting the hook above 48 in., such as high on the compartment door, puts it outside every reach range. Fitting hooks in the standard stalls while leaving the accessible compartment without one also runs against 213.3.7.

Another is ignoring an obstruction. A hook above a bench or counter may need the lower 44 in. or 46 in. limit instead of 48 in. The last is a long hook on a circulation path that sticks out more than 4 in. at a height 307.2 covers.

Choosing coat hooks

Start with projection. If the hook will sit on a circulation path, compare its listed projection with the 4 in. limit in 307.2.

Count before you order. Once hooks go into any toilet compartment, plan a hook within reach for the compartments that 213.3.1 requires. In a toilet room without compartments that has hooks, at least one must be within reach.

Hooks & Towel Bars buying guide and specs

ADA Coat Hook Height and Reach Ranges: common questions